Results
#1. Choose all that apply to a Dry Pipe System (Select Three)
Select all that apply:
#2. Scope
#3. The information sign shall be inspected?
#4. A reduction of ______ percent of pressure during a main drain test must be identified and corrected
#5. Bladder Tank Proportioner
#6. Hose House
#7. Monitor Nozzles shall be inspected ________?
#8. What best describes a tree system?
#9. Which three types of sprinkler systems could be installed in an unheated area?
#10. Waterflow alarm and supervisory alarm devices shall be inspected?
#11. After the testing and reinstallation of plugs and caps for auxiliary drain and test valves, what action is required?
#12. Sprinklers subject to overspray accumulation shall be protected using cellophane bags having a thickness of ___________ or less or thin paper bags?
#13. What is the definition of a hydrostatic test?
#14. Hose connections should be inspected, tested, and maintained in accordance with NFPA 25 Chapter ______ and Chapter____?
#15. Sprinklers shall not show signs of the following?
#16. On what type of systems can possible ice obstructions be found?
#17. Monitor Nozzle
#18. Critical Deficiency
#19. Where sprinklers are subjected to harsh environments, including corrosive atmospheres and corrosive water supplies, on a five-year basis, they shall be?
#20. Which of the following sprinklers produces large water droplets and is listed for its capability to provide fire control of specific high-challenge fire hazards?
#21. Authority Having Jurisdiction (AHJ)
#22. When are hard hats required on the job sites?
#23. The gauge on the quick opening device shall indicate _____ as compared to the gauge on the system side of the dry pipe valve?
#24. A spare sprinkler wrench shall be required for what?
#25. What type of antifreeze solution should be utilized in CPVC piping?
#26. Upright Sprinkler
#27. What is the maximum allowed scissor lift speed?
#28. A permanently marked metal or rigid plastic information sign shall be placed at the system control riser supplying an antifreeze loop, dry system, preaction, or auxiliary system control valve?
#29. Semiautomatic Hose Rack Assembly
#30. Information signs should indicate which of the following?
#31. Recessed Sprinkler
#32. What should be included on the list of fire sprinklers required at the spare sprinkler head box?
#33. Flush Sprinkler
#34. Tanks not equipped with supervised water level alarms connected to a constantly attended location shall be inspected?
#35. Clean
#36. If the presence of foreign material is found ______ an obstruction investigation shall be conducted
#37. What is an automatic sprinkler system that has automatic sprinklers that are attached to a piping system, connected to a water supply through a valve that is opened by the operation of a detection system installed in the same area as the sprinkler?
#38. In systems where the sole water supply is through a backflow preventer and/or pressure reducing valves, the main drain test of at least one system downstream of the device shall be conducted ________?
#39. ITM Service
#40. Main drain test shall be conducted _______ at each water-based fire protection system riser to determine whether there has been a change in the condition of the water supply piping and control valves
#41. What components of a fire hydrant are required to be lubricated?
#42. Hearing protection is required when the noise level reaches 90 DBA for a duration of _________hrs?
#43. Sprinklers subject to overspray accumulation shall be protected using cellophane bags having a thickness of ______ inches?
#44. Approved
#45. Fire Department Connection
#46. 100 GPM is flowing through 100′ of 1 1/4 in. Sch. 40 pipe. How many feet of 1 1/2 in. pipe will produce the same friction loss?
#47. Orifice Plate Proportioning
#48. Hose Reel
#49. The owner’s information certificate indicates the property to be protected will contain nitrate film. Which of the following is also required to be provided?
#50. Discharge Device
#51. Identify what type of sprinkler is designed to be installed in such a way that the water stream is directed downward against the deflector
#52. For protected facilities having over 1000 sprinklers, how many spares should there be?
#53. Dry sprinklers that have been in service for 10 years shall be?
#54. Determine the maximum operating pressure for an Extra Hazard Group 2 sprinkler
#55. Determine the maximum spacing permitted for an Extra Hazard hydraulically calculated system with a density less than 0.25 gpm/ft²
#56. Gauges shall be replaced every _____yrs or tested every _____yrs by comparison with a calibrated gauge
#57. What is the frequency for testing the hose connections for pressure reducing and relief valves?
#58. Should
#59. The temperature of water in tanks with low temperature alarms connected to a constantly attended location shall be inspected and recorded ______ during the heating season when the mean temperature is less than 40°F
#60. NFPA / ITM
#61. At what minimum points or locations should internal obstructive examinations be performed?
#62. This pump is characterized by a method of producing flow by capturing a specific volume of fluid per pump revolution and reducing the fluid void by a mechanical means to displace the pumping fluid
#63. In a water flow test using two hydrants, ______ pressure is the pressure at the hydrant where the water is not flowing
#64. Electric motor-driven fire pumps shall be operated?
#65. What type of valve is designed for the purpose of reducing downstream water pressure under both residual and static conditions?
#66. Sprinklers installed in areas that are inaccessible for safety consideration, due to process operations ____ be ____ during each scheduled shutdown?
#67. Gauges on a wet pipe sprinkler system shall be inspected?
#68. Sprinklers subject to overspray accumulation shall be protected by using?
#69. Reduced Pressure Principle Backflow Prevention Assembly (RPBA)
#70. When the gauge near the compressor is reading higher than the gauge near the dry pipe valve, the air line shall be what?
#71. Equipment should be locked out/ tagged out when which of the following conditions exist?
#72. Is nonmetallic piping required to be internally inspected for the presence of foreign organic or inorganic matter?
#73. What formula is used to determine the discharge coefficient relating pressure and flow rate?
#74. When should a flow test be performed on a Class 1 standpipe system?
#75. Dry Barrel Hydrant (Frostproof)
#76. Are fire hydrants required to be lubricated?
#77. For protected facilities having under 300 sprinklers, there should be how many spare sprinklers?
#78. When should more than one test point be required on an antifreeze system?
#79. Low water temperature alarms, where provided, shall be tested ________ (cold weather only)
#80. Which of the following statements is incorrect when describing a deluge system?
#81. When using a grounded power tool you find an available extension cord (2 wire). What should you do?
#82. Standard Balance Pressure Proportioner
#83. Systems, where provided, shall be tested _______ whenever the high water temperature limit switches on the tank heating system is in service
#84. Which standpipe system relies solely on the fire department connection to supply the water and is dry when not in use?
#85. What is Table 6.1.1.2?
#86. Ensure that the OS&Y automatic tank fill valves shall be inspected isolation valves are in the normal _______ to open position?
#87. Which of the following should you inspect on an extension cord before each use?
#88. At what pressure & test time duration are FDC connections required to be hydrostatically tested?
#89. Conventional Pin Rack
#90. All penetrations into the area of cold storage shall be inspected. If an ice obstruction is found during the inspection, what requirement shall be employed?
#91. Performance Based Program
#92. The test shall be conducted by starting the pump?
#93. Foam Concentrate
#94. Deficiency
#95. If a cross main in a ________ pipe sprinkler system has three branch lines per bay, one intermediate hanger shall be permitted to be omitted, if a branch line hanger is installed on the starter piece
#96. Wall Hydrant
#97. Tank heating systems without a supervised low temperature alarm connected to a constantly attended location shall be inspected ______ during the heating season
#98. What type of testing requires the use of a refractometer?
#99. Backflows shall be inspected ______ to ensure water is not discharging from the relief port
#100. A flow test shall be conducted every _________ at the hydraulically most remote hose connections of each zone of an automatic standpipe system to verify the water supply still provides the design pressure at the required flow?
#101. Which three devices utilize a positive means to hold an emergency isolating device in the safe position?
#102. Normally closed valves shall be secured by the means of a seal or be ________ in accordance with the applicable NFPA standard
#103. Emergency Impairment
#104. How far above the point of support is a ladder required to extend when used to access the roof? _____ft
#105. A water flow test was conducted using 2 hydrants. Both 2 1/2″ outlets were used on hydrant #1 while one outlet was used on hydrant #2. The pitot reading at each hydrant was 12 psi. If the discharge coefficient is 0.7, what is the total water flow (gpm) during this test?
#106. What chapter outlines the General requirements of NFPA 25?
#107. On which of the following valves in a wet system would pressure gauges normally be found?
#108. When using compressed air for cleaning, it should be rated at less than ______ PSI?
#109. Who is responsible for the inspection, testing, maintenance and impairment of a water based fire protection system?
#110. What chapter of NFPA 25 sets out the administration or scope?
#111. Emergency Impairment
#112. Where air pressure supervision is connected to a constantly attended location, gauges shall be inspected?
#113. When there is a ______ percent reduction in full flow pressure when compared to the original acceptance test or previously performed tests, the cause of the reduction shall be identified and corrected if necessary
#114. The exterior of the tank, supporting structure, vents, foundation, and catwalks or ladders, where provided, shall be inspected ________ for signs of obvious damage or weakening
#115. Line Proportioner
#116. Factors that define Occupancy Group Hazard 2 include
#117. Per NFPA 25, the dry pipe valve shall be externally inspected?
#118. Sprinklers installed in areas that are inaccessible for safety considerations due to process operations shall be inspected?
#119. Centrifugal pumps shall furnish not less than ____%
#120. Where can the referenced publications that are used to create NFPA 25 be found?
#121. Pressure tanks that have their air pressure source supervised in accordance with NFPA 72, National Fire Alarm and Signaling Code, shall be inspected?
#122. A three-screw ceiling flange is used to attach the hangers for 6 in. Sch. 40 pipe. If 1 3/4″ lag screws are used, what is the maximum spacing for the hangers?
#123. Units
#124. A sprinkler system that is composed of 2-1/2″ Sch. 40 steel pipe. What is the maximum distance between hangers?
#125. At what interval should a steel water storage tank with no corrosion protection be visually inspected internally?
#126. Wet barrel hydrants shall be inspected ___________ after each operation?
#127. The interior of all other types of tanks shall be inspected every _______?
#128. NFPA 13 specifies the depth of cover for underground pipe with a minimum of 2 1/2 ft, 3 ft under driveways, and 4 ft under railroad tracks. However, it must be at least 1 ft below the frost line. If the frost line is 2 1/2 ft, what is the minimum depth of cover under a driveway?
#129. What is the frequency & purpose of testing fire hydrants?
#130. Which of the following signs require a quarterly inspection to verify that it is securely attached to the sprinkler riser?
#131. What type of information is collected when you are conducting a water flow test from one hydrant?
#132. Water flow test information should be included on what set of plans?
#133. Gauges on a dry, preaction system, and deluge systems shall be inspected?
#134. Qualified
#135. The air pressure in pressure tanks with a nonsupervised air pressure source shall be inspected?
#136. Pressure Restricting Device
#137. The interior of steel tanks without corrosion protection shall be inspected every ________?
#138. ________ indicates a mandatory requirement according to NFPA definitions
#139. Shall
#140. During an inspection, which of the following would be identified as a sprinkler which shall be replaced?
#141. What is the conversion factor between liters and gallons?
#142. The hydraulic design information sign for hydraulically designed systems shall be inspected?
#143. Sectional Drain
#144. Impairment
#145. For corrosive water conditions, steel pipe on the suction side of the pump is required to be
#146. A system that provides 1-1/2 inch hose stations to supply water for use primarily by trained personnel or by the fire department during initial response is a ___________
#147. What two pieces of information are necessary to determine an equivalent replacement for a defective control valve that is no longer manufactured or available?
#148. What type of test shall be provided when a valve is returned to service to determine that the valve is open?
#149. PIV and OS&Y shall be backed a __________ turn from the fully open position to prevent jamming
#150. Is a fire department connection required to be hydrostatically tested?
#151. Name the system that utilizes a plate through which a passes a specific amount of foam concentrate at a specific pressure
#152. NFPA 13 permits branchline hangers to be attached to metal roof decks if the pipe size doesn’t exceed ____ inch(es)
#153. What type of water based fire protection system will have the proportioning valve?
#154. Expansion joints, where provided, shall be inspected _________ for leaks and cracks
#155. A building has 3 different types of sprinklers. How many sprinkler wrenches are required to be kept on premises?
#156. In Line Balanced Pressure Proportioner
#157. Which of the following must be included in the Working Plans associated with water supply requirements?
#158. The maximum allowable shutoff head for a pump with a rated capacity of 900 gpm and a rated head of 250 ft is
#159. Noncritical Deficiency
#160. When there is a _________ percent reduction in full flow pressure, when compared to original acceptance test, the cause of the reduction shall be identified and corrected
#161. Manual Operation
#162. Copper tube that has the greatest (largest inside diameter) for 1 inch nominal tube is
#163. Mechanical waterflow alarm devices including, but not limited to, water motor gongs shall be tested?
#164. Scaffolding and components shall be capable of supporting a weight of?
#165. When should an antifreeze system be tested at more than one point?
#166. Sprinklers shall be tested for sensitivity and functionality at ______ PSI
#167. A class 1 standpipe system is a system that provides _________in hose connections to water supply used by fire departments
#168. Supplementary conditions of a contract contain which of the following
#169. Double Check Valve Assembly
#170. Determine the maximum allowable shutoff pressure for a fire pump with a rated capacity of 750 gpm and a rated head of 60 ft
#171. To avoid false alarms where a supervisory service is provided, the alarm receiving facility shall be notified by the property owner or designated representative before?
#172. Sprinklers shall be inspected when and how?
#173. Internal examination of sprinkler pipe shall be performed at what areas while conducting an obstruction investigation and prevention?
#174. Pressure Vacuum Vent
#175. An installation requires a 3 in. Sch. 40 pipe. If a bend is required, what is the minimum bending radius?
#176. Which Chapter covers the minimum requirements of Standpipe & Hose Systems?
#177. Sprinklers and automatic spray nozzles used for protecting commercial type cooking equipment and ventilating systems shall be replaced?
#178. How long should subsequent records be retained?
#179. Fire Hydrant
#180. In systems where the sole water supply is through a backflow preventer and/or pressure reducing valves, the main drain test of at least one system downstream of the device shall be conducted on a _________ basis
#181. Gauges not accurate within 3 percent of the full scale shall be?
#182. Are buildings with multiple wet pipe systems required to have all systems internally inspected at the same time?
#183. High and low water level alarms shall be tested ________?
#184. What is the minimum operating pressure for any sprinkler?
#185. An ______ test of each pump assembly shall be conducted by qualified personnel under minimum, rated, and peak conditions, with water discharged through approved test devices
#186. Gauges not accurate to within _______ percent of the full scale shall be recalibrated or replaced?
#187. Sprinkler pipe and fittings shall be inspected from where and when?
#188. Preplanned Impairment
#189. Some water storage tanks are equipped with heaters
#190. Components of a standpipe and hose systems shall be visually inspected?
#191. Sprinkler Pipe hangers and seismic bracing shall be inspected?
#192. Monitor Nozzle Hydrant
#193. The temperature of water in tanks without low temperature alarms connected to a constantly attended location shall be inspected and recorded ______ during the heating season when the mean temperature is less than 40°F (4.4°C)
#194. Monitor Nozzles shall be lubricated ________ to ensure proper operating condition?
#195. Which of the following would be an acceptable material for the information sign to be made of?
#196. Diesel engine-driven fire pumps shall be operated?
#197. Horizontal Rack
#198. From what position or level should fire sprinkler piping, fittings, and sprinkler heads be visually inspected?
#199. Dry barrel and wall hydrants shall be inspected?
#200. At what time intervals should check valves be internally inspected?
#201. NFPA 13 defines the information which should be included in the working plans to be submitted to the AHJ for approval. These include which of the following
#202. Automatic Detection Equipment
#203. Who is qualified to perform the corrections and repairs of a water based fire protection system?
#204. Dry pipe system piping that passes through a cold storage freezer shall be inspected?
#205. The supply of spare sprinklers shall be inspected when?
#206. In a manufacturing plant classified as Ordinary Hazard Group 2, the sprinkler system is provided with one inside hose station. Per NFPA 13 2016, Table 11.2.3.1.2, what is the minimum inside hose demand?
#207. Valve enclosures for pre-action/deluge valves equipped with low temperature alarms are to be inspected?
#208. Records made during all inspections, tests, and maintenance shall be made available to who upon request?
#209. 100 gpm is flowing through 100′ of 1 1/4 in Schedule 40 pipe. How many feet of 1 1/2 in pipe will produce the same friction loss?
#210. What is the temperature class and color code for a sprinkler located at a ceiling with a maximum temperature of 150 degrees?
#211. Ordinary Hazard is a term that specifies
#212. Who must sign the Owner’s Certificate?
#213. A basic contract: (choose all that apply)
Select all that apply: